Annual fire alarm inspection report

Fill in the annual inspection and testing record on site — system, power, signals, every device, what is still open — sign it, and download the PDF. Paste the device list from last year’s spreadsheet instead of retyping it.

Free downloads — no sign-up

The visit

Ask the local authority if unsure — the form never picks it for you.
Look up your state’s edition
Building local time

Building

Times print in America/Chicago

Systems in this building

Only the sections for systems marked «Yes» are asked.

  • Is the system monitored by a supervising station?
  • Is there a public emergency alarm reporting system?
  • Is there a mass notification system (MNS)?
  • Is there an emergency communications system (voice / EVAC / two-way)?
  • Are there remote annunciators?
  • Are there remote power panels?

Devices tested (0)

6.3–6.5 · the device supplements

Paste rows from Excel or a CSV export (with or without the header row), or add devices one at a time. Sample spreadsheet

The rest of the record

57 blank · they print as «not entered»

In the order of the NFPA 72 record of inspection and testing. Mark a line N/A when it does not apply — a blank and an N/A mean different things to the reader.

Inspection1 blank
1. Property7 blank
2. Testing and monitoring4 blank
3. Documentation1 blank
4. System15 blank
5. Notification before testing4 blank
6.1 Control unit and associated equipment8 blank
Control unit — visual / functional
Lamps / LEDs / LCD — visual / functional
Fuses — visual / functional
Trouble signals — visual / functional
Disconnect switches — visual / functional
Ground-fault monitoring — visual / functional
Supervision — visual / functional
Local annunciator — visual / functional
6.2 Secondary power4 blank
Battery condition — visual / functional
Load voltage — visual / functional
Discharge test — visual / functional
Charger test — visual / functional
7. Notification of test completion5 blank
Other tests (field contract)3 blank
9. Certification5 blank

Impairments and deficiencies not corrected

Section 10

You choose impairment, deficiency or observation — the form never grades a problem for you.

Sign

Printed with the testing company's name, if your state issues one.
Signature

What you type stays in this browser. The PDF is made on this device; we only count that one was made.

What the annual visit covers

For a typical monitored system, under the 2022 edition. The semiannual items fall on the annual visit too; under 2019, valve tamper and waterflow devices are also inspected quarterly. Your system may have more — check every component it has.

Whole system

  • Inspect · All equipment — condition, damage, obstructions, building or use changes

Control unit

  • Inspect · Control unit (monitored) — fuses, interfaced equipment, lamps/LEDs, primary power
  • Inspect · Control unit (monitored) — trouble signals · semiannual
  • Test · Control unit functions, fuses, interfaced equipment, lamps/LEDs, primary power (tested at maximum load with the battery disconnected)
  • Test · Trouble signals, disconnect switches, ground-fault monitoring, off-premises trouble transmission

Batteries and power

  • Inspect · VRLA battery — month/year marking · semiannual
  • Test · VRLA battery — temperature, charger, cell voltage and ohmic tests · semiannual
  • Test · Secondary power — loss-of-AC trouble; battery capacity covers standby and alarm demand including the safety margin; general alarm 5 min (voice 15 min) on battery

Initiating devices

  • Inspect · Manual pull stations · semiannual
  • Test · Manual pull stations
  • Inspect · Smoke detectors · semiannual
  • Test · Smoke detectors — functional test with smoke entry
  • Inspect · Heat detectors · semiannual
  • Test · Restorable heat detectors — at least 2 on each initiating circuit every year, different ones each year, every detector within 5 years; owner keeps the record of which

Sprinkler supervision

  • Inspect · Supervisory signal devices (valve tamper switches) · semiannual
  • Test · Valve tamper switches — signal within 2 handwheel turns or 1/5 of travel · semiannual
  • Inspect · Waterflow devices · semiannual
  • Test · Waterflow devices (inspector’s test flow) · semiannual

Notification appliances

  • Inspect · Horns, speakers and strobes · semiannual
  • Test · Audible appliances — operation
  • Test · Visual appliances — each one flashes

Control functions

  • Test · Emergency control functions (door releases, HVAC shutdown, elevator recall and others)

The full table, with item numbers and the 2019 differences, is in the frequency planner. Smoke detector sensitivity runs on its own clock — work out when it is due.

What the report has to show

  1. 1

    Every applicable item, or N/A

    The 2022 edition (7.6.6) accepts your own form if it carries all the applicable information on NFPA’s inspection and testing forms. Mark what does not apply as N/A rather than leaving it blank.

  2. 2

    Each device and its result

    Type, address, location and pass or fail for every initiating device, notification appliance and interface — not a count.

  3. 3

    Which frequency the visit covers

    Annual, with the semiannual or quarterly items done on the same visit.

  4. 4

    The edition and the inspector

    The NFPA 72 edition the system was tested to, and the inspector’s name, organization, qualifications and signature.

  5. 5

    Who was notified, and when

    The supervising station, building staff and anyone else told before testing started and after the system was back to normal.

  6. 6

    What is still wrong

    Impairments and deficiencies not corrected before the visit ended. The owner is told in writing within 24 hours (14.2.2.2.3 in the 2019 edition, 14.2.2.3.2 in 2022).

Questions

What does an annual fire alarm inspection include?

A visual inspection of the whole system and a functional test of nearly every component: the control unit and its trouble signals, the batteries and charger, the connection to the supervising station, every pull station, smoke detector, horn and strobe, the emergency control functions such as door releases and elevator recall, and — on the same visit — the semiannual items such as valve tamper switches and waterflow devices. Restorable heat detectors are tested in rotation, at least two per circuit each year.

How late can the annual inspection be?

NFPA 72 defines annual as once per year with at least 9 and at most 15 months between visits (3.3.121.5 in the 2019 edition, 3.3.128.5 in 2022). Your state or the authority having jurisdiction may set a firmer date.

Who keeps the report, and for how long?

Records are kept until the next test and for one year after it (14.6.2.1). Paper or electronic records are both allowed (14.6.2.3). Your state may ask for longer — the longer rule wins.

Is there an official annual inspection form?

NFPA 72 includes sample record forms, but the 2022 edition (7.6.6) also accepts an alternative record that includes all the applicable information those forms show. None of the states we checked publishes its own fire alarm inspection form. Some jurisdictions collect reports through an online portal.

Next year, start from this year

This free form keeps one record in this browser and marks the PDF as a sample. In Strobeline, each building keeps its device list and report facts from one year to the next, signed reports are stored unchanged, the office sees which buildings are coming due, and every PDF carries an address where the stored record can be checked. See pricing.